Download Print this page

Honeywell 900CS10-00 Installation Manual page 12

Hc900 control station

Advertisement

RS232 Communications
If using RS232 communications to have the station communicate with other Honeywell or Modbus-
compatible equipment, create a communications cable as follows.
Terminal no.
Page 12 of 14
RJ12 connector
6
1
Signal
1
CTS
2
RX
3
Ground
4
Ground
5
TX
6
RTS
Connector of slave device
5
9
4
8
3
7
2
6
1
Terminal no.
Signal
7
RTS
3
TXD
5
Ground
1
DCD
2
RXD
8
CTS
51-52-33-157 Rev. 6

Hide quick links:

Advertisement

loading

This manual is also suitable for:

900cs15-00Hc900