LP VAPOR INSTALLATION
BTU and
Pressure Decal
Flex Fuel Line
Size gas pipe from secondary regulator with Generator Sizing
Guide or to local codes.
Fuel Pipe Sizing lP Vapor
Table 5
LP Vapor (LPV) 11" to 14" of Water Column
(Table values are maximum pipe run in feet.)
kW
0.75"
1"
11
70
255
15
25
130
20
15
115
25
55
35
20
45
60
70
80
100
130
150
8
Check Distance
with LP Provider
Check Distance with
Regulator Manufacturer
Safety Shut-Off
with Pressure Port
Pipe Size (in)
1.25"
1.5"
2"
1000
540
480
260
575
125
290
1030
70
165
620
45
115
445
20
60
260
15
50
230
30
165
70
45
Primary Regulator
Per LP Provider
2.5"
3"
1095
LP
660
LPG: 8.55 ft
590
LPG: 36.3 ft
430
1305
205
660
Pressure
150
490
1 inch mercury = 13.61 inches water column
1 inch Water Column = 0.036 psi
11–14 inches water column = 0.396 psi to 0.50 psi
Note:
– Pipe sizing is based on 0.5" H
– Sizing includes a nominal number
of elbows and tees.
– Please verify adequate service and meter sizing.
– Tables based on black pipe.
Size Tank Large Enough to Provide
Required BTU's for Generator and ALL
Connected Appliance Loads.
Be Sure to Correct for MIWR (See Table 6)
High Pressure Pipe
Sized per LP Provider
Secondary Regulator
Vented 5' from Generator
/lb., 4.24 lbs./gal., 2500 btu/ft
3
3
= 1 gal.
3
O pressure drop.