Surge Capability
Table 3
Honeywell Generators (Operating at less than 3600 RPM)
(Running Amps)
Size (kW)
240V 1Ø
208V 3Ø
25
113
87
35
146
121
45
188
156
70
292
243
100
417
347
130
542
451
Honeywell Generators (Operating at 3600 RPM)
Rated Output
(Running Amps)
Size (kW)
240V 1Ø
208V 3Ø
11
42
n/a
15
71
n/a
20
83
n/a
60
250
208
70
292
243
80
333
278
150
625
520
Note: All nominal ratings based upon LP fuel. Refer to specification sheet for
NG ratings and deration adjustments for ambient temperature and altitude.
6
Rated Output
240V 3Ø
480V 3Ø
240V 1Ø
75
n/a
265
105
52
225
135
68
321
210
105
550
300
150
738
390
195
1088
240V 3Ø
480V 3Ø
240V 1Ø
n/a
n/a
92
n/a
n/a
130
n/a
n/a
185
180
90
350
210
105
550
240
120
550
451
226
1214
Maximum Surge Capability
208V 3Ø
240V 3Ø
480V 3Ø
221
192
n/a
210
182
87
269
233
112
471
408
201
452
426
261
885
767
419
Maximum Surge Capability
208V 3Ø
240V 3Ø
480V 3Ø
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
251
218
136
471
408
201
466
404
212
1334
1156
624