NATURAL GAS INSTALLATION
BTU and
Pressure Decal
Flex Fuel Line
Size gas pipe with Generator Sizing Guide or to local codes.
Fuel Pipe Sizing Natural Gas
Natural Gas 5" to 7" of Water Column
Table 4a
(Table values are maximum pipe run in feet.)
kW
0.75"
1"
11
20
85
15
40
20
20
25
35
45
60
70
80
100
130
150
Check Distance with
Gas Provider
Safety Shut-Off
with Pressure Port
Pipe Size (in)
1.25"
1.5"
2"
2.5"
370
800
190
425
130
305
945
85
203
552
35
95
370
915
50
230
585
25
145
390
5
75
225
65
195
40
140
Table 4b
3"
kW
11
15–17
20
1185
710
630
Natural Gas
460
1 cubic foot = 1,000 BTU
50
215
1 therm = 100,000 BTU
30
150
Gas consumption = 13,000-16,000 BTU per kW/hr
Pressure
1 inch mercury = 13.61 inches water column
1 inch Water Column = 0.036 psi
3.5–7 inches water column = 0.126 psi to 0.252 psi
Note:
– Pipe sizing is based on 0.5" H
– Sizing includes a nominal number of elbows and tees.
– Please verify adequate service and meter sizing.
– Tables based on black pipe.
Size Meter for Generator Load
Plus ALL Appliances
For Underground Installations Verify
Piping System for Code Compliance
Natural Gas 3.5" to 5"
of Water Column
(Table values are maximum
pipe run in feet.)
Pipe Size (in)
0.75"
1"
1.25"
1.5"
30
125
200
10
60
125
10
60
125
O pressure drop.