Operation - Honeywell Aquastat L4007 Product Data

Hide thumbs Also See for Aquastat L4007:
Table of Contents

Advertisement

L4006,7,8; L6006,7,8 AQUASTAT
1
L6006
R
CIRCULATOR
AND
LOW LIMIT
W
CONTROL
B
LOW VOLTAGE
LINE VOLTAGE
1
PILOTSTAT
LINE VOLTAGE
GAS CONTROL
POWER SUPPLY. PROVIDE DISCONNECT MEANS
1
AND OVERLOAD PROTECTION AS REQUIRED.
2
WHEN USING CIRCULATOR LOW LIMIT CONTROL,
REMOVE L1-L2 JUMPER.
Fig. 25. Typical wiring hookup using L6006 or
L6007 with L8148A.
LINE VOLTAGE
CONTROL CIRCUIT
L1
(HOT)
1
L2
LOW VOLTAGE
CONTROL CIRCUIT
L4006
L1
(HOT)
1
L2
POWER SUPPLY. PROVIDE DISCONNECT MEANS
1
AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 26. Typical systems with 120 volt
electric heat primaries.
60-2104—10
®
CONTROLLERS
L1
(HOT) L2
SERIES 80
THERMOSTAT
L1
L2
T
T
2
3
B
L8148A
R
C2
B1
B2
C1
2
1
CIRCULATOR
2
1
2
OIL BURNER RELAY
LINE VOLTAGE
TERMINALS
M8783C
LINE VOLT
LOAD
L4006
THERMOSTAT
LOW VOLTAGE
THERMOSTAT
LOAD
1K
ELECTRIC
HEAT RELAY
M1155A
MILLIVOLTAGE
THERMOSTAT
SAFETY
SHUTOFF
PILOTSTAT¨
POWER UNIT
Fig. 27. Typical Powerpile System wiring diagram.
L6008G
W
W
B
B
R
R
2
1
JUMPER
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
Fig. 28. Typical oil burner installation using L4008G.

OPERATION

For proper selection of settings, follow the boiler manufacturer
recommendations.
High Limit Controller
R-B terminals provide high limit switching function (contacts
open at set point on temperature rise). (See Figures 30 and 31).
R-B terminals shut off burner if water temperature exceeds high
limit setting. Burner restarts when temperature drops to high
limit setting, less differential.
NOTE: On manual reset models, the reset button on the front
of the case must be pushed in to allow the burner to
operate after a high limit shutdown.
14
L4006
HIGH LIMIT
CONTROLLER
MILLIVOLTAGE
VALVE OPERATOR
OPERATOR
COIL
POWER UNIT COIL
HEATING LOAD
NO. 1
HEATING LOAD
NO. 2
PILOT
BURNER
M1156A
L2
1
L1
(HOT)
M8968B