APPLICATION
The L4188/L6188 and L4191/L6191 aquastat thermostats
are sensitive direct immersion type water temperature
thermostats for limiting and controlling boiler water
temperature in hydronic heating systems.
The L4188/L6188 aquastat thermostats are single aquastats.
The L4191/L6191 aquastat thermostats are dual aquastats
i.e. two independent controls (controller and limiter housed
under a single cover).
The L4188/L6188 and L4191/L6191 aquastat thermostats
confirm with the following EC directives:
Low Voltage Directive 73/23/EEC
Electro Magnetic Compatability Directive 89/336/EEC
Compliance with the EMC directive regarding emission can
only be determined in the application.
SPECIFICATIONS
Model
See table 1 page 2
Ambient temperature
0 ... 70 °C
Capillary length
0.22 m, 1 m, or 1.5 m
AQUASTAT CONTROL
Electrical connection
6.3 mm quick connect terminals suitable for
The L6188 and L6191 series thermostats are provided with
adapters for screw connection
Electrical rating
10 A at 250 Vac, resistive load
2.5 A at 250 Vac, inductive load
15 A at 250 Vac, locked rotor
2 A at 24 Vac, inductive load
250 mA at 30 mVdc (special option)
Terminal data (see fig.1 and 2 )
C-1 breaks on temperature rise (SPST and SPDT)
C-2 makes on temperature rise (SPDT only)
Immersion wells (must be ordered separately for bulk pack
aquastats)
Type
Insertion
length (mm)
Single
105
169
Dual
105
** Insertion length including thread of brass spud
Maximum well pressure: 10 bar for single and multi wells
(ND 10)
1
INSTRUCTION SHEET
1
/
" receptacles.
4
Thread**
Order number
1
/
" BSPT
45.900.409-003
2
1
/
" BSPT
45.900.409-006
2
1
/
" BSPT
45.900.409-007
2
MU1R-9023 0208R12-NE

Advertisement

loading

Summary of Contents for Honeywell L4188

  • Page 1 (ND 10) temperature in hydronic heating systems. The L4188/L6188 aquastat thermostats are single aquastats. The L4191/L6191 aquastat thermostats are dual aquastats i.e. two independent controls (controller and limiter housed under a single cover).
  • Page 2 Table 1. L4188/L6188 and L4191/L6191 models Type Temperature range ( ° Switching differential ( ° Switch type Setting means L4188A Knob setting 25 ... 95 SPST 40 ... 110 L4188B Internal setting L6188A 4 ... 10 (adjustable) Knob setting 25 ... 95 40 ...
  • Page 3 Differential setting For manual reset models: The adjustable differential can be set by turning the disc Depress the button on the front cover located under the front cover. (ii) For tool reset models: The disc is turned using a screw driver. Remove front cover and depress the button on the The number in line with the point represents the differential bottom left hand side of front plate.

This manual is also suitable for:

L6188aL6188bL6188cL4191L6191aL6191b