HA71 Digital Gas Controller
Analog Output:
Notes:
12 bit integer for Channel Reading value = 800 counts = zero value, 4000 counts = 100% value.
Channel Reading
Channel Status words contain configuration and status bits for a channel. They are as follows:
Type
Channel Status
Bit by Bit Definition:
HA71 Technical Manual
Type
Channel
First
1-16
31001
Channel
First
Last
1-16
31017
31032
Alarm 1 Trip
bit0
Alarm 1 Horn Drive
bit1
Alarm 3 Type
bit2
Alarm 2 Horn Drive
bit3
Linearize
bit4
Alarm 3 Trip
bit5
Input In Cal
bit6
Channel Disable
bit7
Controller Channel In Cal
bit8
Modbus® Data Type
bit9
reserved
bit10
reserved
bit11
Alarm 1 Latch
bit12
Alarm 2 Latch
bit13
Alarm 3 Latch
bit14
Alarm 2 Trip
bit15
Last
Read FC
Write FC
31016
4
n/a
Read FC
Write FC
4
n/a
16bit integer (see bit by bit definition below)
1 = Low
1 = On
1 = Level
1 = On
1 = On
1 = Low
1 = 1.5mA Cal Detected
1 = Disabled
1 = Cal Mode
1 = 4 byte float
1 = Latching
1 = Latching
1 = Latching
1 = Low
5-5
Notes
12bit integer
Notes
0 = High
0 = Off
0 = Fault
0 = Off
0 = Off
0 = High
0 = Normal Mode
0 = Enabled
0 = Normal Mode
0 = 2 byte integer
0 = Non latching
0 = Non latching
0 = Non latching
0 = High
Revision 3 (04/08)