Honeywell STT750 Quick Start Installation Manual page 17

Smartline temperature transmitter
Hide thumbs Also See for STT750:
Table of Contents

Advertisement

Reset Sensor Cal
Sensor CVD
(Applicable for
Pt50, Pt100, Pt200,
Pt500 and Pt1000
RTDs only)
Break Detect
Latching
CJ Type
Fixed CJ Value
(Visible for TC input
only)
LRV
URV
Set LRV
Executing this selection Resets
Confirm
the LRV, and URV Corrects
back to Factory values
Enabled,
Callendar - Van Dusen RTD
Disabled
coefficients for Sensor
Enable,
Enable or disable detection of
Disable
Input wire break
When enabled, causes all
critical sensor input failures to
latch to the Critical Fault state.
Enable,
The fault may only be cleared
Disable
by device reset. When
disabled, the critical sensor
input failure will be cleared if
the input recovers.
Determines the source of the
Internal,
Cold Junction compensation
Fixed
for thermocouple Sensor
types.
When CJ Type is Fixed,
specifies the Cold Junction
temperature value for
thermocouple Sensor types.
####.##
Degrees Celsius. Fixed CJ
temperatures below -50
degrees have no effect on
measured values.
The limits are the Lower
#. ##
Range Limit (LRL) and the
#. ##
Upper Range Limit (URL) of
the selected Sensor 1 ID
ATTENTION: Executing this
Set
Lower
service will set the Lower
Range
Range Value (LRV) equal to
Value
the input pressure
Quick Start Installation Guide
SmartLine Temperature Transmitter
Press ↵ to
enter
menu
selection
↑ and ↓ to
select
entry.
↵ to enter
Read Only
Parameter
Press ↵ to
enter
menu
selection
↑ and ↓ to
select
entry.
↵ to enter
17