CONTROL ELEMENTS
CHAPTER 5: SETTINGS
Figure 5-140: Time of day timer example
The
FlexLogic operand follows the state of the timers. In addition, one-second pulses are generated on the
TIME OF DAY 1 ON
and
FlexLogic operands when the timers turn on and off, respectively (see the
TIME OF DAY 1 START
TIME OF DAY 1 STOP
following figure). These operands can be combined in FlexLogic with the day and month FlexLogic operands and/or with
FlexElements operating on the DAYOFYEAR, DAYOFMONTH, and SECONDOFDAY FlexAnalog parameters to create virtually
any time and date condition for custom time or season-based control actions. To activate these FlexAnalog parameters,
enable at least one time of day timer.
Figure 5-141: Close/open/maintain control via FlexLogic operands
5
If the relay is connected to an external clock that follows daylight savings time changes, take care that the changes do not
result in undesired operation.
The following settings are available for each time of day timer element.
— Used to program the relay clock/calendar value for which the timer turns on.
TIME OF DAY TIMER 1 START TIME
— Used to program the relay clock/calendar value for which the timer turns off.
TIME OF DAY TIMER 1 STOP TIME
— If enabled, the
and
events are logged.
TIME OF DAY TIMER 1 EVENTS
TIME OF DAY 1 ON
TIME OF DAY 1 OFF
Figure 5-142: Time of day timer logic
5-262
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL