GROUPED ELEMENTS
5
Up to three identical bank overvoltage elements, one per each VT bank configured in hardware, are provided.
5-244
BANK OV 1 BANK
GROUND: Grounded
BANK OV 1 CURVE:
FlexCurve A
BANK OV 1 CURVE TIME
MULTIPLIER: 1.00
BANK OV 1 STG 1A
PICKUP: 1.050 pu
BANK OV 1 STG 2A
PICKUP: 1.100 pu
BANK OV 1 STG 3A
PICKUP: 1.200 pu
BANK OV 1 STG 4A
PICKUP: 1.050 pu
BANK OV 1 STG 1B
PICKUP: 1.050 pu
BANK OV 1 STG 2B
PICKUP: 1.100 pu
BANK OV 1 STG 3B
PICKUP: 1.200 pu
BANK OV 1 STG 4B
PICKUP: 1.050 pu
BANK OV 1 STG 1C
PICKUP: 1.050 pu
BANK OV 1 STG 2C
PICKUP: 1.100 pu
BANK OV 1 STG 3C
PICKUP: 1.200 pu
BANK OV 1 STG 4C
PICKUP: 1.050 pu
BANK OV 1 STG 1
PKP DELAY: 60.00 s
BANK OV 1 STG 2
PKP DELAY: 10.00 s
BANK OV 1 STG 3
PKP DELAY: 2.00 s
BANK OV 1 STG 4
PKP DELAY: 0.20 s
BANK OV 1 DPO DELAY:
0.25 s
BANK OV 1 BLK:
Off
BANK OV 1 TARGET:
Self-Reset
BANK OV 1 EVENTS:
Disabled
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Range: Grounded, Ungrounded, Ungr w/o Vn
Range: FlexCurve A, FlexCurve B, FlexCurve C,
FlexCurve D
Range: 1.00 to 10.00 in steps of 0.01
Range: 0.800 to 2.000 pu in steps of 0.001
Range: 0.800 to 2.000 pu in steps of 0.001
Range: 0.800 to 2.000 pu in steps of 0.001
Range: 0.800 to 2.000 pu in steps of 0.001
Range: 0.800 to 2.000 pu in steps of 0.001
Range: 0.800 to 2.000 pu in steps of 0.001
Range: 0.800 to 2.000 pu in steps of 0.001
Range: 0.800 to 2.000 pu in steps of 0.001
Range: 0.800 to 2.000 pu in steps of 0.001
Range: 0.800 to 2.000 pu in steps of 0.001
Range: 0.800 to 2.000 pu in steps of 0.001
Range: 0.800 to 2.000 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled