Honeywell FSL100-IR3 Technical Handbook page 43

Fsl100 series
Table of Contents

Advertisement

Cone Of Vision
Ingress Protection
Temperature, Operating, ATEX/IECEx/FM
Temperature, Operating, Safe Areas
Temperature, Storage
Humidity Range
Automatic and Manual Self-Test
Detector Body
Swivel Mounting
Dimensions (Body only)
Weight
Cable Gland
Pressure Compensating Element
Terminals
EN54-10 Certificate
ATEX Certificate
FM3260 Approval
FM3611 Approval
RoHS
MAN0987_Iss 2_09/16
SPECIFICATIONS
CERTIFICATION
FSL100 General Specifications
90°
IP65
-25 °C to +70 °C (-13 °F to +158 °F)
-40 °C to +70 °C (-40 °F to +158 °F)
-40 °C to +70 °C (-40 °F to +158 °F)
0 – 95 %RH, non-condensing
Automatic Sensor Test (Built in Self-Test) and manual self-test
GRP, Non-Incendive. UV resistant, Self-Extinguishing V-0 (UL-94).
PA66 (UV Resist.), 316 SS (Fixings)
125 x 80 x 57 mm (4.9 x 3.15 x 2.25 inch)
465 gram (1.05 lb)
745 g (1.67 lb) with optional mounting
cores 0.5 to 1.5 mm
The Pressure Compensating Element (PCE) helps prevent moisture
build up inside the detector housing caused by ambient fluctuation
Suitable for cores 0.5 to 1.5 mm
0.4 Nm (0.3 ft/lb)
FSL100-IR3 Flame Detector: Class 1
FSL100-UV Flame Detector: Class 2
FSL100-UVIR Flame Detector: Class 2
FSL100-IR3 Flame Detector: ATEX zone 2/22
FSL100-UV Flame Detector: ATEX zone 2/22
FSL100-UVIR Flame Detector: ATEX zone 2/22
FSL100-IR3 Flame Detector
FSL100-UV Flame Detector
FSL100-UVIR Flame Detector
FSL100-IR3 Flame Detector: Non-Incendive, Class 1,2 & 3 Div 2
FSL100-UV Flame Detector: Non-Incendive, Class 1,2 & 3 Div 2
FSL100-UVIR Flame Detector: Non-Incendive, Class 1,2 & 3 Div 2
FLS100 Series is RoHS compliant
Table 3. FSL100 General Specifications
39
2
(20 to 16 AWG)
2
(20 to 16 AWG), tightening torque
FSL100 Series Flame Detectors
Technical Handbook

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fsl100-uvFsl100-tlxFsl100-uvirFsl100-sm21Fsl100-tl

Table of Contents