Toshiba Tosvert VF-S15 Instruction Manual page 213

Industrial inverter (for 3-phase induction motors)
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

1) Emergency stop from terminal
Emergency stop occurs at contact a or b. Follow the procedure below to assign a function to an input
terminal and select a stop method.
[Parameter setting]
Title
f515 Deceleration time at emergency stop
f603
Emergency stop selection
DC braking time during emergency
f604
stop
f251 DC braking current
Setting example) When assigning the emergency stop function to S2 terminal
Title
f114 Input terminal selection 4A (S1)
Setting value 21 is reverse signal.
Note 1) Emergency stopping via the specified terminal is possible, even during panel operation.
2) Emergency stop from the operation panel
Emergency stop from the operation panel is possible by pressing the STOP key on the panel twice
while the inverter is not in the panel control mode.
(1) Press the STOP key ............................. "eoff" will blink.
(2) Press the STOP key once again ........... Operation will come to a trip stop in accordance with the setting
Note:
While an emergency stop signal is input at a terminal, the trip cannot be reset. Clear the signal and
then reset the trip.
Function
0.0-3600 (360.0) (s)
0: Coast stop
1: Deceleration stop
2: Emergency DC braking
3: Deceleration stop (f515)
4: Quick deceleration stop
5: Dynamic quick deceleration stop
0.0-20.0 (s)
0 - 100 (%)
Function
0 - 203
of the f603 parameter.
After this, "e" will be displayed and a failure detection signal
generated (FL relay is activated).
F-101
Adjustment range
Adjustment range
20: EXT (Emergency
stop by external signal)
E6581926
Default setting
10.0
0
1.0
50
Setting
6