Sharp AY-X36RU Service Manual page 18

Split type air conditioners
Hide thumbs Also See for AY-X36RU:
Table of Contents

Advertisement

AY-X36RU
AE-X36RU
Capacitor charge fault (Fault with outdoor unit) (AP1 the control panel of the outdoor unit)
5.
Main Check Points:
● Use AC voltmeter to check if the voltage between terminal L and N on the wiring board is within 210VAC~240VAC.
● If the reactor (L) is correctly connected? If the connection is loose or fallen? If the reactor (L) is damaged?
Use DC voltmeter
voltage on the two
ends of electrolytic
Voltage higher than 200V?
Measure the AC voltage between
terminal L and N on wiring board
XT(power supply)
210VAC~250VAC?
Shut down the power and wait 20 minutes;or
use DC voltmeter to measure the voltage
on the two ends of capacitor , until
the voltage is lower than 20V
connection of reactor
Replace the control
Turn on the unit
and wait 1 minute
to measure the
capacitor
Fault with the voltage
Y
N
Shut down the power
and repair the power
Voltage within
N
supply to restore the
range
210VAC~250VAC
Y
Check the
(L in the Electrical
Wiring Diagram)
Connect the reactor
Laccording to Elec-
If the wiring of
N
trical Wiring Diagr-
reactor L is normal?
am correctly
Y
panel AP1
End
Replace the control
testing circuit on
panel AP1
control panel AP1
power on and
restart the unit
N
Re-energize and
turn on the unit
N
18
Is the problem fixed?
Y
Is the problem fixed?
Y