SPM Flex Gas Detector
Bar graph
The bar graph displays the concentration reading up to double the Alarm 2
value for the gas being monitored� The Alarm 1 and Alarm 2 values are indicated
numerically on the bar graph�
The display can be configured for different backlight and dimming options� By
default the backlight will dim after a few minutes of no activity� The display can
be configured to turn off the backlight entirely after a set period of time�
Inhibit
When the detector is in inhibit mode, it will show a bell icon with a red slash
through it�
1� Use the [Up] or [Down] buttons to select the "Inhibit" on the Maintenance
menu�
2� Press the [Accept] button�
3� The Inhibit Type menu or the Time Out menu can then be selected�
Possible inhibit types are none, alarms only, faults only, alarms and faults,
and all, as shown in the following table)� The Time Out options (the time
until the detector exits inhibit mode and returns to active monitoring) are
from 1 to 60 minutes�
4� To take the unit out of inhibit, select "None" from the Inhibit Type menu and
press the [Accept] button twice to return to the Maintenance menu�
NOTE
If the inhibit times out before the inhibit state is returned to "none,"
maintenance fault code M17 will be displayed�
34