Praesideo 3.5 | Installation and User Instructions | EN54-16: 2008
Clause / Requirement
15 Marking
The VACIE shall be marked with the following information,
which shall be legible at access level 1:
a
the number of this European Standard;
b
the name or trademark of the manufacturer or supplier;
c
the type number or other designation of the VACIE.
It shall be possible to identify a code or number that
identifies the production period of the VACIE at access
level 1 or 2 or 3.
Where Annex ZA.3 covers the same requirements as this
clause, the requirements of this clause are met.
Clause / Requirement
16 Tests
Bosch Security Systems | 2011-02
Compliance
Praesideo is compliant.
The installer must mark the Praesideo system with the
number of this European standard (which is legible at
access level 1) since the installer must install and configure
the system properly in order to let the installation comply
with this standard.
The name 'Bosch' is visible on each element of the
Praesideo system. The installer must ensure that this name
is legible at access level 1 for all system elements.
The type number of each unit of the Praesideo system is
present on the unit itself. The installer imust ensure that this
type number is legible at access level 1.
The hardware version and production data are visible on
the type number plate of each unit of the Praesideo system.
The installer must ensure that this type number plate is
identifiable at access level 1, 2 or 3.
Compliance
All tests as asked for in the clauses of section 16 have been
carried out by an accredited certification body for EN54-16
compliancy.
The Praesideo system has been found compliant to
EN-54-16 and received a certification of compliancy.