This section describes the procedures for mounting and wiring the control panel and all the peripheral devices.

Mounting the Control in the Standard Cabinet for Commercial Fire only Applications

If you are installing a Vista-32FBPT in the Fire-only cabinet with the internally-mounted transformer, follow the steps
below.
Step
Action
1
Before mounting the circuit board, remove the metal knockouts for the wiring entry that you will be using.
DO NOT ATTEMPT TO REMOVE THE KNOCKOUTS AFTER THE CIRCUIT BOARD HAS BEEN
INSTALLED.
2
Using fasteners or anchors (not supplied), mount the control cabinet to a sturdy wall in a clean, dry area
that is not readily accessible to the general public. The back of the cabinet has four holes for this purpose.
Installing the Cabinet Lock
To install the lock, perform the following steps:
Step
Action
1
Remove the cabinet door, and the lock knockout from the door. Insert the key into the lock (see Figure 3-1).
2
Position the lock in the hole, making certain that the latch will make contact with the latch bracket when
the door is closed.
3
When correctly positioned, push the lock until its snap tabs hold it securely.
Use a Honeywell No. K4445 Lock (supplied).
Commercial Fire Guidelines
For Commercial Fire installations, the following requirements apply (See Figure 3-2).
System components mounted inside the cabinet must be placed so that all power-limited wiring is separated from all
non-power-limited wiring (AC and battery) by a minimum of ¼-inch (6.4mm).
Non-power-limited wiring that exits the control panel (i.e., transformer wiring) must be run in conduit.
All unused knockouts must be plugged.
All wiring that exits the control panel must be strain-relieved (e.g., tie-wrapped).

Section 3: Installing the Control

CHECK
POSITION
LOCKED
PUSH
UNLOCKED
CABINET DOOR
BOTTOM

Figure 3-1: Installing the Lock

PUSH
ON LOCK
UNTIL IT
SNAP
IS SEATED
TAB
SECURELY
SNAP
TAB
STEP 1
STEP 2
21