Programming Field Settings For Ulc304 Compliance - Honeywell VISTA-32FBPT Installation And Setup Manual

Commercial fire and burglary partitioned security system with scheduling
Hide thumbs Also See for VISTA-32FBPT:
Table of Contents

Advertisement

Program feature or option
3
01 EVENT DISPLAY LOCK
3
12 ZN TYPE 18 DELAY
USE
3
13 "SUPV" ON OPEN AND
SHORT (APPLIES TO ZONE
TYPE 18
3
14 W.F. ALARM SILENCE
OPT.
3
16 ZONE TYP 17/18 DLY
3
18 EXTENDED DLY FOR
TYP 17/18
3
20 TRIG OUTS FUNC SEL
3
21 MAX ATEMPTS
3
50 ZONE TYPES 16-18
REST.
3
60 BELL 2, AUX RLY
TIMEOUT
3
82 BURG FEATURES
ENABLED
RESTRICTION FOR FIRE
RELAYS

Programming Field Settings for ULC304 Compliance

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION,
This product incorporates field-programmable software. In order for the product to comply with the
requirements in the Standard for Signal Receiving Centre and Premise Burglar Alarm Control Units ULC
S304, certain programming features or options must be limited to specific values or not used at all as
indicated below.
Program feature or
option
38 PREVENT ZONE XXX
BYPASS (PARTITION
SPECIFIC)
1
58 ENABLE 5800 RF FORCE
ARM
2
03 ULC S304 ENABLE
2
08 FORCE-ARM ENABLE
(PARTITION SPECIFIC)
Permitted in
UL864? Y/N
0 = disable
N
1 = enable
0 = disable
N
1 = enable
N
0 = Trouble on open/Supv on
short
1 = Supv on open/Supv on short
0 = Silenced by User Code +
N
OFF
1 = Silenced when zone restores
Enter 01-15 times 2 seconds
N
Enter 00 for no delay
0 = no extended delay
N
1 = multiply delay by 4
0 = remote keypad sounder
N
1 = keyswitch LEDs
1-8
Y
0 = disable
N
1 = enable
Enter 01-15 multiplied by 2
Y
minutes.
00 = no timeout.
0 = disable
N
1 = enable
Yes
Y
No
AND OTHER INVOLVED PARTIES
Possible settings
Enter a zone number (001-032).
Enter 000 if all zones can be
bypassed.
0 = disable
1 = enable
0 = disable
1 = enable
0 = disable
1 = enable
Possible settings
Settings permitted in ULC S304
Must be set to "000" (all zones can be bypassed).
Must be set to "0" (disable).
Must be set to "1" (enabled).
Must be set to "0" (disable).
10
Settings permitted in UL 864
Must be set to "1" (enable).
Must be set to "0" (disable).
Must be set to "0".
Must be set to "0" (Silenced by
User Code + OFF).
Must be set to 00 (no delay).
Must be set to 0 (no extended
delay).
Must be set to 0 (remote keypad
sounder).
Must be set at 3, 4 or 5.
Must be set to "1" (enable).
Must be set to "3" (Minimum of 6
minutes).
Must be set to "0" (disable).
Restriction for # 70 must be set
to Yes when programming fire
relays.