System Mechanical Installation

4.2.1 Wall Mount Fixings

You will require the following locally sourced items to install the Touchpoint Plus:
Tool to undo the enclosure access handle security screws:
3 mm Hex key
Suggested Fixings to screw the enclosure to the wall only:
Screw Max. Dia:
Screw Min. Length:
Washer Max. Dia:
Note: The sizes above are given to allow for clearance in the TPPL Enclosure. The actual length and type of
fixing should be determined by the surface material and the type of anchor required.
Suggested Fixings for using the Mounting Plate:
For the plate, choose fixings appropriate to the surface and the weight of the enclosure plus cables. You will
also need to use suitable bolts, washers and lock nuts (see diagram below).
Ideally you will mount the enclosure and cables on a ≥20 mm ply board to allow cable troughs to be used.
Note:
You should ensure that washers between the TPPL enclosure and the wall or mounting plate are sufficiently
large to spread the load evenly.
For metal conduit, use a metal ground plate (i.e. Part No: TPPLOMGND).
For external visual/audio outlet, ensure IP65 is maintained (i.e. Part No: M-700123).
For cable gland, use type PG16 and tighten to 44.2 lb-in torque.
6.4 mm (#14) dome or cheese head screw
76 mm (3 in.) – Normal fix
14.3 mm (0.56 in.)
Enclosure Corner

Figure 14. Fixing Orientation When Using the Optional Mounting Plate

Wall or
Board
21
Touchpoint Plus
Technical Handbook