GE C30 Instruction Manual page 136

Controller system
Hide thumbs Also See for C30:
Table of Contents

Advertisement

PRODUCT SETUP
Observer — This role has read-only access to all C30 settings. This role allows unlimited concurrent access but it has
no download access to any files on the device. Observer is the default role if no authentication has been done to the
device. This role displays as "None" on the front panel.
The Factory service role is not available. It is for factory use only.
NOTE
Change local passwords
SETTINGS  PRODUCT SETUP  SECURITY  CHANGE LOCAL PASSWORDS
 CHANGE LOCAL
 PASSWORDS
The Change Local Passwords menu is shown on the front panel and in EnerVista upon successful login of the Administrator
role.
The
setting in this menu is similar to that described in
LOGIN
role.
Passwords are stored in text format. No encryption is applied.
5
In Device authentication mode, the Observer role does not have a password associated with it. In Server
authentication mode the Observer role requires a password.
NOTE
If you are locked out of the software, contact GE Digital Energy for the default password. When using
CyberSentry, the default password is "ChangeMe1#".
Once the passwords are set, the Administrator with Supervisor approval can change the role-associated
password.
In CyberSentry, password encryption is not supported.
Session settings
SETTINGS  PRODUCT SETUP  SECURITY  SESSION SETTINGS
 SESSION
 SETTINGS
— This setting specifies the number of failed authentications before the device blocks subsequent
SESSION LOCKOUT
authentication attempts for the lockout period. A value of zero means lockout is disabled.
SESSION LOCKOUT PERIOD
there is no lockout period.
Restore defaults
SETTINGS  PRODUCT SETUP  SECURITY  RESTORE DEFAULTS
 RESTORE DEFAULTS
5-18
LOGIN:
None
NEW PASSWORD:
CONFIRM PASSWORD:
SESSION LOCKOUT:
3
SESSION LOCKOUT
PERIOD: 3 min
— This setting specifies the period of time in minutes of a lockout period. A value of 0 means that
LOAD FACTORY
DEFAULTS: No
Range: 20 alphanumeric characters
Range: 20 alphanumeric characters
Range: 20 alphanumeric characters
SETTINGS > PRODUCT SETUP > SECURITY
Range: 0 to 99
Range: 0 to 9999 minutes
Range: Yes, No
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
except for the factory

Advertisement

Table of Contents
loading

Table of Contents