Iec 61850 Goose Integers - GE Multilin g60 Instruction Manual

Ur series generator protection system
Hide thumbs Also See for Multilin g60:
Table of Contents

Advertisement

5.8 INPUTS/OUTPUTS
Table 5–33: GOOSE ANALOG INPUT BASE UNITS
ELEMENT
dcmA
FREQUENCY
FREQUENCY RATE OF CHANGE
PHASE ANGLE
POWER FACTOR
RTDs
SENSITIVE DIR POWER
(Sns Dir Power)
SOURCE CURRENT
SOURCE ENERGY
(Positive and Negative Watthours,
Positive and Negative Varhours)
SOURCE POWER
SOURCE VOLTAGE
STATOR DIFFERENTIAL
CURRENT
(Stator Diff Iar, Ibr, and Icr)
STATOR GROUND 3RD
HARMONIC VOLTAGES
(Stator Gnd Vn/V0 3rd)
5
STATOR RESTRAINING
CURRENT
(Stator Diff Iad, Ibd, and Icd)
SYNCHROCHECK
(Max Delta Volts)
VOLTS PER HERTZ
The GOOSE analog input FlexAnalog™ values are available for use in other G60 functions that use FlexAnalog™ values.

PATH: SETTINGS
INPUTS/OUTPUTS
 GOOSE UINTEGER
 INPUT 1
The IEC 61850 GOOSE uinteger inputs feature allows the transmission of FlexInteger™ values between any two UR-
series devices. The following settings are available for each GOOSE uinteger input.
UINTEGER 1 DEFAULT: This setting specifies the value of the GOOSE uinteger input when the sending device is
offline and the
UINTEGER 1 DEFAULT MODE
number.
UINTEGER 1 DEFAULT MODE: When the sending device is offline and this setting is "Last Known", the value of the
GOOSE uinteger input remains at the last received value. When the sending device is offline and this setting value is
"Default Value", then the value of the GOOSE uinteger input is defined by the
The GOOSE integer input FlexInteger™ values are available for use in other G60 functions that use FlexInteger™ values.
5-264
BASE UNITS
BASE = maximum value of the
under the +IN and –IN inputs.
f
= 1 Hz
BASE
df/dt
= 1 Hz/s
BASE
= 360 degrees (see the UR angle referencing convention)
BASE
PF
= 1.00
BASE
BASE = 100°C
= maximum value of 3  V
P
BASE
configured for the sensitive power directional element(s).
I
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
E
= 10000 MWh or MVAh, respectively
BASE
P
= maximum value of V
BASE
V
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
I
= maximum primary RMS value of the +IN and –IN inputs
BASE
(CT primary for source currents, and bus reference primary current for bus differential currents)
V
= Primary auxiliary voltage of the
BASE
I
= maximum primary RMS value of the +IN and –IN inputs
BASE
(CT primary for source currents, and bus reference primary current for bus differential currents)
V
= maximum primary RMS value of all the sources related to the +IN and –IN inputs
BASE
BASE = 1.00 pu

IEC 61850 GOOSE UINTEGERS
UINTEGER
1000
UINTEGER
MESSAGE
MODE: Default Value
is set to "Default Value".This setting is stored as a 32-bit unsigned integer
G60 Generator Protection System
setting for the two transducers configured
DCMA INPUT MAX
 I
for the +IN and –IN inputs of the sources
BASE
BASE
 I
for the +IN and –IN inputs
BASE
BASE
STATOR GROUND SOURCE

5.8.13 IEC 61850 GOOSE INTEGERS


GOOSE UINTEGER INPUT 1(16)
Range: 0 to 429496295 in steps of 1
1 DEFAULT:
Range: Default Value, Last Known
1 DEFAULT
UINTEGER 1 DEFAULT
5 SETTINGS
setting.