GE Multilin g60 Instruction Manual page 318

Ur series generator protection system
Hide thumbs Also See for Multilin g60:
Table of Contents

Advertisement

5.6 GROUPED ELEMENTS
5
Figure 5–74: PHASE INSTANTANEOUS OVERCURRENT TIMING CURVES
SETTING
PHASE IOC1
FUNCTION:
Enabled = 1
Disabled = 0
SETTING
PHASE IOC1
SOURCE:
IA
IB
IC
SETTING
PHASE IOC1
BLOCK-A:
Off = 0
SETTING
PHASE IOC1
BLOCK-B:
Off = 0
SETTING
PHASE IOC1
BLOCK-C:
Off = 0
Figure 5–75: PHASE INSTANTANEOUS OVERCURRENT 1 SCHEME LOGIC
5-158
SETTING
SETTINGS
PHASE IOC1
PHASE IOC1
PICKUP:
PICKUPDELAY:
AND
RUN
PHASE IOC1 RESET
DELAY:
IA ≥ PICKUP
t
PKP
t
AND
RUN
RST
t
IB ≥ PICKUP
PKP
t
RST
AND
RUN
t
PKP
IC ≥ PICKUP
t
RST
G60 Generator Protection System
5 SETTINGS
FLEXLOGIC
OPERANDS
PHASE IOC1 A PKP
PHASE IOC1 A DPO
PHASE IOC1 B PKP
PHASE IOC1 B DPO
PHASE IOC1 C PKP
PHASE IOC1 C DPO
PHASE IOC1 A OP
PHASE IOC1 B OP
PHASE IOC1 C OP
OR
PHASE IOC1 PKP
OR
PHASE IOC1 OP
AND
PHASE IOC1 DPO
827033A6.VSD
GE Multilin