Download Print this page

Honeywell 2RM7800L1087 Installation Instructions Manual page 6

Relay modules with valve proving

Advertisement

RM7800L1087; RM7840G1022,L1075; EC7840L1014 RELAY MODULES WITH VALVE PROVING
Combination No.
1
C
2
B
3
No Load
4
F
5
No Load
6
D
7
No Load
8
D
9
No Load
A
4.5A ignition.
50 VA Pilot Duty
4.5A ignition.
a
Pilot Duty refers to solenoid-type valves.
Mounting RM7800L/40L, EC7840L
Relay Module (Fig. 9)
1. Mount the RM7800L/40L, EC7840L vertically on the
Q7800 Subbase, or mount horizontally with the
knifeblade terminals pointing downward. When
mounted on the Q7800A, the RM7800L/40L, EC7840L
must be in an electrical enclosure.
2. When mounting in an electrical enclosure, provide
adequate clearance for servicing, installation and
removal of the RM7800L/40L, EC7840L, Keyboard
Display Module, flame amplifier, flame amplifier signal
voltage probes, electrical signal voltage probes, and
electrical connections.
66-1162—2
Table 4. Combinations for Terminals 8, 9, 10 and 21.
Pilot Fuel 8
F
F
F
F
F
F
D
D
D
Table 5. Explanation of Each Combination.
B
180 VA ignition plus
a
plus
motor valve with:
660 VA inrush, 360 VA
open, 260 VA hold.
Main 9
Ignition 10
No Load
No Load
No Load
A
A
A
A
A
A
C
2A Pilot Duty.
a. Allow an additional two inches below the
RM7800L/40L, EC7840L for the flame amplifier
mounting.
b. Allow an optional three-inch minimum to both sides
of the RM7800L/40L, EC7840L for electrical signal
voltage probes.
3. Make sure no subbase wiring is projecting beyond the
terminal blocks. Tuck in wiring against the back of the
subbase so it does not interfere with the knifeblade
terminals or bifurcated contacts.
IMPORTANT
The RM7800L/40L, EC7840L must be installed with
a plug-in motion rather than a hinge action.
4. Mount the RM7800L/40L, EC7840L by aligning the four
L-shaped corner guides and knifeblade terminals with
the bifurcated contacts on the wiring subbase and
securely tighten the two screws without deforming the
plastic.
6
Valve 21
No Load
No Load
B
No Load
F
No Load
D
No Load
D
D
F
a
64 VA Pilot Duty
motor valves with:
3850 VA inrush, 700 VA
open, 250 VA hold.
a
plus

Hide quick links:

Advertisement

loading

This manual is also suitable for:

Rm7840g1022,l1075Ec7840l1014