Honeywell 2RM7800L1087 Installation Instructions Manual page 21

Relay modules with valve proving

Advertisement

RM7800/
RM7840/
Test
EC7840
No.
Models
Jumpers Voltmeter
1
All
None
2
All
3
All
4
All
5
All
4-5
6
All
4-10 *
7
All
4-8 *
8
All
4-21 *
9
All
4-9 *
10
All
4-3
11
All
4-5
and
12-13
12
All
4-5
and
14-13
RM7800L1087; RM7840G1022,L1075; EC7840L1014 RELAY MODULES WITH VALVE PROVING
Table 9. Static Checkout.
Test
4-L2
Line voltage at Terminal 4.
6-L2
Line voltage at Terminal 6.
17-L2
For VP applications. (Terminal 17)
16-L2
Line voltage at 16
20-L2
Line voltage at Terminal 20.
7-L2
1. Burner motor (fan or blower)
starts.
2. Line voltage at Terminal 7 within
10 seconds.
Ignition spark (if ignition
transformer is connected to
Terminal 10)
1. Ignition spark (if ignition
transformer is connected to
Terminal 8).
2. Automatic pilot valve opens (if
connected to Terminal 8).
NOTE: Refer to wiring diagram of
Same as test no. 6 for connections
to Terminal 8. If using direct spark
ignition, check the first stage fuel
valve(s) instead of the pilot valve or
MV2 for VP tests.
Automatic main fuel valve(s) open.
If using direct spark ignition on a
model with intermittent pilot on
Terminal 21, check the optional
second stage fuel valve, if used.
Alarm (if used) turns on.
18-L2
Firing rate motor drives open; zero
volts at Terminal 18 after motor
starts driving open.
18-L2
Firing rate motor drives closed; line
voltage at Terminal 18 after motor
is in Low Fire position.
Normal Operation
system being tested.
21
If Operation is Abnormal,
Check the Items Listed Below
1. Master Switch.
2. Power connected to the Master Switch.
3. Overload protection (fuse, circuit
breaker, etc.) has not opened the power
line.
1. Limits.
2. Burner Controller.
Valve Proving switch.
1. Pre-Ignition interlocks.
1. Burner motor circuit.
a. Manual switch of burner motor.
b. Burner motor power supply, overload
protection, and starter.
c. Burner motor.
2. Running or Lockout Interlocks (including
Airflow Switch).
1. Watch for spark or listen for buzz.
a. Ignition electrodes are clean.
b. Ignition transformer is okay.
1. Watch for spark or listen for buzz.
a. Ignition electrodes are clean.
b. Ignition transformer is okay.
2. Listen for click or feel head of valve for
activation.
a. Actuator if used.
b. Pilot valve.
Same as test no. 6. If using direct spark
ignition, check the first stage fuel valve(s)
instead of the pilot valve.
1. Listen for and observe operation of the
main fuel valve(s) and actuator(s).
2. Valve(s) and actuator(s).
1. Alarm.
1. Low Fire Start Switch.
2. Firing rate motor and transformer.
1. Low Fire Start Switch.
2. Firing rate motor and transformer.
66-1162—2