Honeywell ADEMCO LYNXR-ISIA Installation And Setup Manual page 32

Table of Contents

Advertisement

LYNXR-ISIA Installation and Setup Guide
✻ 56 Enhanced Zone Programming Mode
While in Program mode, press
Refer to the zone assignment table for
The following explains the
available entries for each. The right-most column provides a further explanation of the entries.
Note:
You may find it convenient to adjust the volume setting before entering the Programming Mode. This will allow you to clearly hear
feedback announcements or system beeps.
Zone number
02-41, 95, 96, 99 = Zone number
A 02
[✻] = continue
00 = exit Zone Programming mode
Zone type
b
00-24 = zone type
zt
[✻] = continue
[#] = return to previous prompt
Note: If 00 is accepted as a zone type, save the 00
Report code
Enter the report code for this zone.
rc
C
[✻] = continue
[#] = return to previous prompt
Input type
d
3 =RF (supervised RF) – sends periodic
i
check-in signals, faults, restore and low
battery signals
Note: RF type transmitters must remain within range
4 = UR (unsupervised RF) – sends same as
"RF" type, but control does not supervise
the check-in signals
5 = BR (button type) – sends only fault and low
battery signals; does not send restores or
check-in signals
Note UR and BR type transmitters may be carried off
[✻] = continue
[#] = return to previous prompt
56 to enter Zone Programming Menu Mode.
56 on the separate programming form.
56 prompts in detail. The left two columns identify the prompts and list the
zone type and advance to the confirm delete
prompt (F).
of the receiver, otherwise a supervision failure
signal will occur.
premises (out of range without causing a
supervision failure.
Enter the 2-digit zone number to be programmed and the Voice
Descriptor for the selected zone number will be announced, if it is
programmed. Press [
] to advance.
Zones 02-25 = RF zones (only)
Zones 26-41 = Button zones (only)
Zone 92 = Duress
Zones 95, 96, 99 = Panic zones
Pressing 00 exits mode, upon which the prompt "56" blinks, indicating
the mode is inactive. Press [
Each zone must be assigned to a zone type, which defines the way in
which the system responds to faults in that zone. Enter the 2-digit zone
type for this zone as follows:
00 = Not Used
01 = Entry/Exit #1
02 = Entry/Exit #2
03 = Perimeter
04 = Interior Follower
05 = Trouble Day/Alarm Night
06 = 24 Hr Silent
07 = 24 Hr Audible
08 = 24 Hr Aux
Notes: 1. ZT9 and ZT16 can not be assigned to Zone 01 (hard wire
zone).
2. ZT16 is not for use with manually actuated devices
including fire, keypad or keyfob zones, or fire pull stations,
or for heat detectors.
SIA ZT 16 must be used in SIA fire applications.
The report code consists of 2 hexadecimal digits, each in turn consisting
of 2 numerical digits. For example, for a report code of "3C", enter [0][3]
for "3" and [1][2] for "C".
If this is Zone 95, 96 or 99, the system skips to the VOICE
DESCRIPTOR prompt (1C).
Enter the input type for the transmitter assigned to this zone. Refer to
the transmitter's instructions for input types of each transmitter.
Note: Zones 2-25 should be assigned Input Type 3 or 4 . Zones 26-41
should be assigned Input Type 5 only.
- 32 -
] + any field number to go to that field.
09 = Fire without verification
10 = Interior w/Delay
16 = Fire with verification
20 = Arm–Stay
21 = Arm–Away
22 = Disarm
23 = No Alarm Response
24 = Silent Burglary

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents