Huawei UPS2000-G User Manual page 65

Lead-acid battery
Hide thumbs Also See for UPS2000-G:
Table of Contents

Advertisement

UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery)
Model
Wiring
Termina
l
15 kVA
Dual-
(dual-live-
live-wire
wire input
input
dual-live-
Battery
wire output)
Dual-
live-wire
Output
15 kVA
Input
(single-
phase input
single-phase
Battery
output)
Output
15 kVA
Bypass
(three-phase
input
input single-
phase
Mains
output)
input
Battery
Output
15 kVA
Bypass
(three-phase
input
input three-
Mains
phase
input
output)
Issue 23 (2024-03-15)
Numb
Rated
er of
Voltage
Phases
2
208 V
AC/220 V AC
-
± 240 V DC
2
208 V
AC/220 V AC
1
220 V
AC/230 V
AC/240 V AC
-
± 240 V DC
1
220 V
AC/230 V
AC/240 V AC
1
220 V
AC/230 V
AC/240 V AC
3
380 V
AC/400 V
AC/415 V AC
-
± 240 V DC
1
220 V
AC/230 V
AC/240 V AC
3
380 V
AC/400 V
AC/415 V AC
3
Copyright © Huawei Digital Power Technologies Co., Ltd.
External
Cable
Circuit
Cross-
Breaker
Sectional
Area
100 A/2 P
2
25 mm
(character
istic D)
63 A/4P
2
16 mm
100 A/2 P
2
25 mm
(character
istic D)
100 A/2 P
2
25 mm
(character
istic D)
63 A/4P
2
16 mm
100 A/2 P
2
25 mm
(character
istic D)
100 A/2 P
2
25 mm
(character
istic D)
50 A/4 P
2
10 mm
(character
istic D)
63 A/4P
2
16 mm
100 A/2 P
2
25 mm
(character
istic D)
50 A/4 P
2
10 mm
(character
istic D)
4 Installation
Terminal
Torque
Type
for
Tighteni
ng Bolts
4.8 N·m
2
25 mm
M6 OT
terminal
2
4.8 N·m
16 mm
M6 90°
OT
terminal
2
4.8 N·m
25 mm
M6 OT
terminal
4.8 N·m
2
25 mm
M6 OT
terminal
2
4.8 N·m
16 mm
M6 90°
OT
terminal
2
4.8 N·m
25 mm
M6 OT
terminal
4.8 N·m
2
25 mm
M6 OT
terminal
2
2.8 N·m
10 mm
M6 OT
terminal
4.8 N·m
2
16 mm
M6 90°
OT
terminal
4.8 N·m
2
25 mm
M6 OT
terminal
2
2.8 N·m
10 mm
M6 OT
terminal
57

Advertisement

Table of Contents
loading

Table of Contents