4.1.1 Site

Floor Loading Capacity
The floor must be able to bear the weight of the UPS and its optional
components. In the case of rack-mounted installation, ensure that the floor can
also bear the weight of the rack.
Installation Environment
UPS2000-G-6 kVA/10 kVA Dimensions
Figure 4-1 UPS2000-G-6 kVA/10 kVA installation dimensions
Issue 23 (2024-03-15)
Do not install the UPS in a high-temperature, low-temperature, or damp place
that is beyond the technical specifications.
Keep the UPS far away from water, heat sources, and flammable and
explosive substances. Install the UPS in an environment free of dust, volatile
gas, salt, and corrosive materials. Avoid direct sunlight.
Do not install the UPS in environments with conductive metal scraps in the
air.
The optimal operating temperature for batteries is 20–30ºC. Temperatures
higher than 30ºC shorten the battery lifespan, and temperatures lower than
20ºC reduces the battery backup time.