UPS2000-G-(6 kVA–20 kVA)
User Manual (Lead-Acid Battery)
Issue 23 (2024-03-15)
Table 5-25 Basic screen (UPS2000-G-15KRTL-01/UPS2000-G-20KRTL-01)
Item
Description
Positive
Set the number of batteries.
(Negative)
When the number of
batteries
batteries
the system output power is
derated by
mode. The parameter is
configurable in non-
battery mode or non-
battery ECO mode.
Battery
Set the battery capacity.
capacity
This parameter indicates
the sum of all battery
capacities. Set the
parameters based on the
actual battery capacity. The
parameter is configurable
in non-battery mode or
non-battery ECO mode.
Intelli.
When it is set to Enabled,
Hibernatio
the intelligent battery
n
hibernation function is
enabled. The parameter is
configurable in any mode.
Over
Specifies an alarm
temp.
threshold for battery
thres.
overtemperature. The
parameter is configurable
in any mode.
Under
Specifies an alarm
temp.
threshold for battery
thres.
undertemperature. The
parameter is configurable
in any mode.
Charge
Specifies the charge current
curr. limit
limit. The parameter is
configurable in any mode.
Over
Set an alarm threshold for
current
battery overcurrent. The
thres.
parameter is configurable
in any mode.
Battery
Specify whether battery
string
string sharing is supported
sharing
in a parallel system.
Copyright © Huawei Digital Power Technologies Co., Ltd.
N is less than 20,
N /20 in battery
5 Control Panel
Default Value
Value Range
0
16–20
65 Ah
7–1000 Ah
Disabled
Disabled,
Enabled
50°C
45–55°C
–5°C
–30°C to +5°C
2.0 A
1.0–4.0 A
6.0 A
4.0–8.0 A
Disabled
Disabled,
Enabled
97