Analog Input Configuration Procedure - GE Multilin D20E Installation And Maintenance Manual

Ethernet i/o module
Table of Contents

Advertisement

Set Analog Input for
D20E IO Calculator
function (example)

Analog input configuration procedure

68
Setting
Descriptions
Value Type
Specify the date type the Publisher application uses
when reporting the analog input.
RTDB Point
Specify the RTDB point whose value is reported for
the analog input. A custom window allows you to
associate the analog input to any analog input or
counter available in the D20E.
Table 15: Provider IO and Publisher Protocol - Value Type:
Value Type
Discrete
Signed Integer
Unsigned Integer
Signed Long Integer
Short Floating
Double Floating
Message
Table 16: Provider- IO Scale:
IO Scale
Minus_5_to_5V
0_to_1mA
0_to_5mA
0_to_10mA
0_to_20mA
Raw
Percentage
To set up the Analog Input for the calculation function (that is, for the raw standard (16 bit
Integer) in the legacy D.20 Input/Outputs):
1.
Navigate to Settings > Providers > IO Provider > IED > Analog Input > Calculation.
2.
Set MULTIPLIER to a value pf 2.
3.
Navigate to Settings > Providers > IO Provider > IED > Analog Input > Protocol.
4.
Set SCALE to Calculation.
You must set the scaling to Calculation in order for these settings to work. For details see
the DAPserver Studio online help.
When configuring a D20E for Analog Input from a Substation Controller device (for
example: D20ME, D20MEII, or D20MX) or a Substation Gateway device (for example: D400
or DMC490), a signed 16 bit range (-32,768 to +32,767) is required from the D20E Publisher
in a Signed Integer format.
Since the Raw value is a signed 15 bit value, it must be doubled.
GE INFORMATION
CHAPTER 3: CONFIGURING THE D20E FIRMWARE
Appropriate settings for D20E
Not applicable for analog input value
Negative or positive (bipolar) integer value
No polarity (unipolar) integer value
Negative or positive double standard size integer value
32-bit (sign, exponent, mantissa) IEEE 754 value; Default value,
should be used always for Provider IO
64-bit (sign, exponent, mantissa) IEEE 754 value
Not applicable for analog input value
Appropriate settings for D20E
±5V full scale value (floating)
±1mA full scale value (floating)
±5mA full scale value (floating)
±10mA full scale value (floating); to be included in next release
±20mA full scale value (floating)
±16383 (14-bit) full scale value (floating or integer)
±100% full scale value (floating); to be fixed
D20E ETHERNET I/O MODULE INSTRUCTION MANUAL
Range
Default
Discrete
Signed integer
Unsigned integer
Signed long
integer
Short floating (32-
bit IEEE format)
Double floating
(64-bit IEEE format)