GE Multilin D20E Installation And Maintenance Manual page 60

Ethernet i/o module
Table of Contents

Advertisement

62
Setting
Descriptions
Historical settings
Note: The D20E does not currently support the Historical data settings.
Calculation settings
Note: No calculation is applied on the Counter Input.
Providers - Protocol settings
Reference
Specify a text string that combines the bay name,
Name
group name, and provider name from the General
tab.
Physical
Specify the index of the physical IO pin.
Index
Debounce
Specify (in ms) the amount of time a point must stay
Filter Length
in a given state before a change to state is recorded.
Chatter Filter
Select the amount of time (in ms) to be used in the
Time Range
Chatter Filter calculation.
Chatter Filter
Specify the number of changes during the Chatter
On Trigger
Filter Time period that enables the Chatter Filter.
The recommended value is 10 to 20 changes, to
reduce event noise.
Chatter Filter
Specify the number of changes allowed during the
Off
Chatter Filter Time period before the Chatter Filter is
Hysteresis
turned off.
Pulse Count
This setting must be enabled for Counter points.
Enable
Pulse Count
Specify the Reset Pulse count to be value 0 (zero)
Reset
when the D20E is rebooted and when the Pulse
Count Enable setting is Enabled.
Pulse Polarity Specify the state that increases the count of the
Counter point.
Physical
This setting is not used for Counter points.
Index 2
Counter Type Specify the type of counter. See section:
type
on page 60.
Note: Only Binary counters should be selected. This
enables both Binary and Frozen counter types in the
Publisher for DNP3.0 Object 21 and integrity polls.
Publisher settings
Reference
Specify a text string that combines the bay name,
Name
group name, and provider name from the General
tab.
Point
Specify the point description of the mapped analog
Description
input or counter.
Value Type
Specify the date type the Publisher application uses
when reporting the counter.
RTDB Point
Specify the RTDB point whose value is reported for
the counter. A custom window allows you to
associate the counter to any analog input or counter
available in the D20E.
GE INFORMATION
CHAPTER 3: CONFIGURING THE D20E FIRMWARE
Range
0 (off) to 1000.ms
100 ms
1000 ms
0 (off) to 900
changes
High
Low
Counter
Discrete
Signed integer
Unsigned integer
Long Signed
integer
Floating (Short 32-
bit IEEE format)
Double (Floating
64-bit IEEE format)
D20E ETHERNET I/O MODULE INSTRUCTION MANUAL
Default
0

Advertisement

Table of Contents
loading

Table of Contents