6 Configuring a Generic Ethernet Module
4.
Enter the IP Address of the
CU320-2 PN or CU310-2 PN.
5.
The Connection Parameters
section configures the IO
Assemblies for the CU320-2. The
Assembly Instances should
always be 101 through 103 for the
Input, Output and Configuration
Assembly respectively. The size
of the Input and Output
assemblies is the total number of
words for all the control unit drive
objects to be configured as IO.
This can be determined by
adding the column listing the
number of words for each
telegram in the message frame
configuration of the Starter
project.
6.1.3

Connection Parameters

Table 6-3 Setting the Connection Parameters
1.
The Requested Packet Interval (RPI) is
the rate at which the controller will
exchange data with the IO module. In
this application we will use a value of 10
ms.
2.
2) Unicast is selected as the exchange
method.
SINAMICS S: Speed control of a S120 with an Allen-Bradley controller
(Compact/ ControlLogix with RSLogix 5000) via EtherNet/IP
Entry-ID: 92045369,
V4.0,
08/2018
1
2
27