12.3 Communication parameter setting

Set each parameter following the procedures below.
Setting item numbers such as [17, [19], etc. are the same as those on the "6.4 Operation flowchart". (p.12)
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
Proceed to Auxiliary function setting mode.
Press
The unit proceeds to Auxiliary function setting mode.
+
[17]
Auxiliary function setting mode
Press
The unit proceeds to Communication protocol selection.
(Twice)
[19]
Communication protocol selection
Select the communication protocol.
: Modbus ASCII mode (Default)
: Modbus RTU mode
: MEWTOCOL (Slave)
[20]
Instrument number setting
Set the instrument number of the controller individually when
communicating by connecting plural instruments.
1 to 99 (Default: 1)
[21]
Communication speed selection
Set the communication speed equal to that of the host computer.
: 2400bps
: 4800bps
: 9600bps (Default)
: 19200bps
[22]
Data bit/Parity selection
Select the data bit and parity.
: 8 bits/No parity
: 7 bits/ No parity
: 8 bits/Even
: 7 bits/Even (Default)
: 8 bits/Odd
: 7 bits/Odd
[23]
Stop bit selection
Select the stop bit.
: 1 (Default)
: 2
[24]
Communication response time setting
Set the minimum response time.
5 to 99 (Default: 5ms)