When power is turned on or when control output OFF function is cancelled by the
SV changes as follows in relation to PV.
(e.g.) SV=200
, SV rise rate=6
[When SV>PV]
Temperature
C
SV=200
C
PV=25
[When SV PV]
Temperature
PV=250
C
C
SV=200
0
/Min, SV fall rate=30 /Min
25
200
SV display 25 C
Power is
turned on
In the case of SV>PV, when power is turned on,
or when control output OFF function is cancelled by
the
SV rises from 25
(Fig. 11.11-4)
SV display 250
250
C
200
C
Power is
turned on
In the case of SV PV, when power is turned on,
or when control output OFF function is cancelled by
the
key, the SV fall rate setting works, and
SV falls from 250
(Fig. 11.11-5)
SV display 200 C
C
(on the SV display) approaches
by the SV rise rate.
C
Time
key, the SV rise rate setting works, and
to 200
by the rate of 1 /sec.
C
(on the SV display) approaches
by the SV fall rate.
Time
to 200
by the rate of 0.5 /sec.
35
key,