Panasonic KT4H User Manual page 54

Table of Contents

Advertisement

Modbus
function code
03H/06H
0033H
03H/06H
0034H
03H/06H
0037H
03H/06H
0038H
03H/06H
0039H
03H/06H
0040H
03H/06H
0041H
03H/06H
0044H
03H/06H
0045H
03H/06H
0047H
03H/06H
0048H
03H/06H
0049H
Data item
SV rise rate
SV fall rate
Control output OUT/OFF
Auto/Manual control
Manual control MV
Alarm 1 Energized/Deenergized
Alarm 2 Energized/Deenergized
Input type
Direct/Reverse action
AT bias
ARW
Heater burnout alarm 2 value
54
Data
Set value, Decimal point ignored
Set value, Decimal point ignored
0000H: Control output ON
0001H: Control output OFF
0000H: Automatic control
0001H: Manual control
Set value
0000H: Energized
0001H: Deenergized
0000H: Energized
0001H: Deenergized
0000H: K -200 to 1370
0001H: K -200.0 to 400.0
0002H: J -200 to 1000
0003H: R 0 to 1760
0004H: S 0 to 1760
0005H: B 0 to 1820
0006H: E -200 to 800
0007H: T -200.0 to 400.0
0008H: N -200 to 1300
0009H: PL-
0 to 1390
000AH: C(W/Re5-26) 0 to 2315
000BH: Pt100 -200.0 to 850.0
000CH: JPt100 -200.0 to 500.0
000DH: Pt100 -200 to 850
000EH: JPt100 -200 to 500
000FH: K -320 to 2500
0010H: K -320.0 to 750.0
0011H: J -320 to 1800
0012H: R 0 to 3200
0013H: S 0 to 3200
0014H: B 0 to 3300
0015H: E -320 to 1500
0016H: T -320.0 to 750.0
0017H: N -320 to 2300
0018H: PL-
0 to 2500
0019H: C (W/Re5-26) 0 to 4200
001AH: Pt100 -320.0 to 1500.0
001BH: JPt100 -320.0 to 900.0
001CH: Pt100 -320 to 1500
001DH: JPt100 -320 to 900
001EH: 4 to 20mA -2000 to 10000
001FH: 0 to 20mA -2000 to 10000
0020H: 0 to 1V -2000 to 10000
0021H: 0 to 5V -2000 to 10000
0022H: 1 to 5V -2000 to 10000
0023H: 0 to 10V -2000 to 10000
0000H: Reverse action
0001H: Direct action
Set value
Set value
Set value, Decimal point ignored

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kt4b

Table of Contents