Set Value Lock; Sv High Limit; Sv Low Limit; Sensor Correction - Panasonic KT9 Instruction Manual

Hide thumbs Also See for KT9:
Table of Contents

Advertisement

Character
(PV display)
Set value lock selection
• Locks the set value to prevent setting errors
The setting item to be locked depends on the selection.
• PID auto-tuning or auto-reset does not work if Lock 1 or Lock 2 is selected.
• When selecting Lock, select Lock 1, Lock 2 or Lock 3 after setting the
necessary items in the status Unlock.
SV high limit setting
• Sets SV high limit.
• Setting range: SV low limit to input range high limit value
SV low limit setting
• Sets SV low limit.
• Setting range: Input range low limit value to SV high limit
Sensor correction setting
• Sets correction value for the sensor.
• Setting range: –100.0 to 100.0
Communication protocol selection
• Selects the communication protocol.
• Available only when Serial communication (option) is applied.
• Not available if
• Modbus ASCII mode:
Instrument number setting
• Sets the instrument number. (Communication cannot be carried out
unless an instrument number is individually set when communicating
by connecting plural instruments in serial communication.)
• Available only when Serial communication (option) is added.
• Setting range: 0 to 95
Communication speed selection
• Selects a speed equal to that of the host computer.
(Communication cannot be performed unless the speeds are equal)
• Available only when Serial communication (option) is added.
• 2400bps:
Name, Function, Setting range
(Unlock): All set values are changeable.
(Lock 1): None of the set values can be changed.
(Lock 2): Only main setting mode can be changed.
(Lock 3): All set values except input type can be changed. However,
they return to their previous value after the power is turned off because
they are not written in the non-volatile memory. Be sure to use
Lock 3 when changing the set value frequently via communication.
(If the value changed by the communication function is the same
as the previous one, it is not written in the non-volatile memory.)
Do not change any setting item in Auxiliary function setting mode
2. If any item in the mode is changed, it will affect other setting
items such as SV and Alarm value.
DC input: SV low limit to scaling high limit value
(The placement of the decimal point follows the selection)
DC input: Scaling low limit value to SV high limit
(The placement of the decimal point follows the selection)
(The placement of the decimal point follows the selection)
, 4800bps:
21
( ), For DC input, –1000 to 1000
is indicated
, Modbus RTU mode:
, 9600bps:
Default value
(SV display)
Unlock
1370
–200
0.0
0
9600bps
, 19200bps: