Start Function; Collector Frost Protection; Overtemperature Protection For The Collector - Siemens RVS41.813 User Manual

Avs75, avs37, qaa75, qaa78, qaa55 series heat pump controller
Table of Contents

Advertisement

Waiting time relative prio
Waiting time parallel op
Delay secondary pump

Start function

Min run time collector
pump
Collector start funct grad

Collector frost protection

Overtemperature protection for the collector

154/258
Siemens Switzerland Ltd
HVAC Products
During the period of time set, the transfer of priority is delayed. This prevents relative
priority from intervening too often.
If solar output is sufficient and solar charging pumps are used, parallel operation is
possible. In that case, the storage tank of the priority model can be the next to be
charged at the same time, in addition to the storage tank to be charged next. Parallel
operation can be delayed by introducing a waiting time. This way, in the case of parallel
operation, switching on of the storage tanks can be effected in steps.
Setting (---) disables parallel operation.
To remove any existing cold water from the primary circuit, operation of the secondary
pump of the external heat exchanger can be delayed.
Line no.
Operating line
3831
Min run time collector pump
3834
Gradient collector start funct
The function activates periodically the collector pump for at least the selected minimum
running time.
When the temperature at the collector sensor rises, the collector pump is activated.
Line no.
Operating line
3840
Collector frost protection
When there is risk of frost at the collector, the collector pump is activated to prevent the
heat-carrying medium from freezing.
If the collector temperature falls below the frost protection temperature, the
collector pump is activated: TKol < TKolFrost.
When the collector temperature returns to a level of 1 K above the frost protection
temperature, the collector pump is deactivated again: TKol > TKolFrost + 1.
Line no.
Operating line
3850
Collector overtemp prot
If there is a risk of overtemperature at the collector, storage tank charging is continued
to reduce the amount of excess heat. When the storage tank's safety temperature is
reached, charging is stopped.
User manual RVS61.843, RVS41.813
6 The settings in detail
CE1U2355en_02
28. September 2009