Room Influence - Siemens RVS41.813 User Manual

Avs75, avs37, qaa75, qaa78, qaa55 series heat pump controller
Table of Contents

Advertisement

Room influence

Pure weather
compensation
Weather compensation
with room influence
Pure room compensation
Siemens Switzerland Ltd
HVAC Products
Line no.
HC1
HC2
HC3P
750
1050 1350
Compensation variants
When using a room temperature sensor, there is a choice of 3 different types of
compensation.
Setting
Type of compensation
− − − %
Pure weather compensation *
1...99 %
Weather compensation with room
influence *
100 %
Pure room compensation
* Outside sensor required.
The flow temperature is calculated via the heating curve, depending on the composite
outside temperature.
This type of compensation calls for a correct adjustment of the heating curve since in
that case the control gives no consideration to the room temperature .
The deviation of the actual room temperature from the setpoint is measured and taken
into account when controlling the temperature. Heat gains can thus be considered,
ensuring more accurate room temperature control. The effect of the deviation is set as
a percentage figure. The better the reference room (correct room temperature, correct
mounting location, etc.) the higher the value can be set.
• Example:
Approx. 60 %
Good reference room conditions
Approx. 20%
Unfavorable reference room
To activate the function, following must be considered:
A room sensor must be connected
The "Room influence" setting must be between 1 and 99
There should be no thermostatic radiator valves in the reference room (mounting
location of room sensor) (If such valves are present, they must be set to their fully
open position)
The flow temperature is controlled depending on the room temperature setpoint, the
current room temperature and the progression of the room temperature. For example, a
slight increase of the room temperature causes an immediate drop of the flow
temperature.
To activate the function, following must be considered:
A room sensor must be connected
"Room influence" must be set to 100%
There should be no thermostatic radiator valves in the reference room (mounting
location of the room sensor). (If such valves are present, they must be set to their
fully open position)
User manual RVS61.843, RVS41.813
6 The settings in detail
Operating line
Room influence
89/258
CE1U2355en_02
28. September 2009