Types of sensor / readjustment
Only RVS61..
Sensor type collector
Sensor readjustments
Building and room model
Siemens Switzerland Ltd
HVAC Products
Line no.
Operating line
6097
Sensor type collector
NTC
Pt 1000
6098
Readjustm collector sensor
6099
Readjustm coll sensor 2
6100
Readjustm outside sensor
Selection of type of sensor used. The controller uses the respective temperature
characteristic.
The measured value of the respective sensors can be readjusted by +/- 3 K.
Line no.
Operating line
6110
Time constant building
When the outside temperature varies, the room temperature changes at different rates,
depending on the building's thermal storage capacity (type of building construction).
The above setting is used to adjust the response of the flow temperature setpoint to
varying outside temperatures.
• Example:
> 20
The room temperature will respond more slowly to outside temperature variations.
10 - 20
This setting can be used for most types of buildings.
< 10
The room temperature will respond more quickly to outside temperature variations.
Setting 0: Function switched off. The attenuated as well as mixed temperature are the
same as the present outside air temperature.
User manual RVS61.843, RVS41.813
6 The settings in detail
193/258
CE1U2355en_02