Hitachi WJ200 Series Quick Reference Manual page 70

Wj200 series inverter single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

Func.
Name
Code
C076
Communication error
select
C077
Communication error
time-out
C078
Communication wait time
C081
O input span calibration
C082
OI input span calibration
C085
Thermistor input (PTC)
span calibration
C091
Debug mode enable *
C096
Communication selection
C098
EzCOM start adr. of master
C099
EzCOM end adr. of master
C100
EzCOM starting trigger
C101
Up/Down memory mode
selection
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
"C" Function
Description
Selects inverter response to
communications error.
Five options:
00...Trip
01...Decelerate to a stop and trip
02...Disable
03...Free run stop (coasting)
04...Decelerates to a stop
Sets the communications watchdog
timer period.
Range is 0.00 to 99.99 sec
0.0 = disabled
Time the inverter waits after
receiving a message before it
transmits.
Range is 0. to 1000. ms
Scale factor between the external
frequency command on terminals
L–O (voltage input) and the
frequency output,
range is 0.0 to 200%
Scale factor between the external
frequency command on terminals
L–OI (voltage input) and the
frequency output,
range is 0.0 to 200%
Scale factor of PTC input.
Range is 0.0 to 200%
Displays debug parameters.
Two option codes:
00...Disable
01...Enable <Do not set>
(for factory use)
00...Modbus-RTU
01... EzCOM
02... EzCOM<administrator>
01-08
01-08
00... Input terminal
01... Always
Controls speed setpoint for the
inverter after power cycle.
Two option codes:
00...Clear last frequency (return to
default frequency F001)
01...Keep last frequency adjusted
by UP/DWN
69
Run
Defaults
Mode
Lnitial data
Units
Edit
02
0.00
sec.
0.
msec.
100.0
%
100.0
%
100.0
%
00
00
01
01
00
00