Hitachi WJ200 Series Quick Reference Manual page 53

Wj200 series inverter single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

Func.
Name
Code
A242
Manual torque boost value, 2
motor
A043
Manual torque boost
frequency
A243
Manual torque boost
frequency,
nd
2
motor
A044
V/f characteristic curve
A244
V/f characteristic curve,
nd
2
motor
A045
V/f gain
nd
A245
V/f gain, 2
motor
a046
Voltage compensation gain for
automatic torque boost
a246
Voltage compensation gain for
automatic torque boost,
motor
a047
Slip compensation gain for
automatic torque boost
a247
Slip compensation gain for
automatic torque boost,
motor
A051
DC braking enable
A052
DC braking frequency
A053
DC braking wait time
A054
DC braking force for
deceleration
A055
DC braking time for
deceleration
A056
DC braking / edge or level
detection for [DB] input
a057
DC braking force at start
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
"A" Function
Description
nd
normal V/f curve,
range is 0.0 to 20.0%
Sets the frequency of the V/f
breakpoint A in graph (top of
previous page) for torque boost,
range is 0.0 to 50.0%
Six available V/f curves;
00...Constant torque
01...Reduced torque (1.7)
02...Free V/F
03...Sensorless vector (SLV)
Sets voltage gain of the inverter,
range is 20. to 100.%
Sets voltage compensation gain
under automatic torque boost,
range is 0. to 255.
nd
2
Sets
slip
compensation
under automatic torque boost,
range is 0. to 255.
nd
2
Three options; select codes:
00...Disable
01...Enable during stop
02...Frequency detection
The frequency at which DC
braking begins,
range is from the start frequency
(B082) to 60Hz
The delay from the end of
controlled deceleration to start of
DC braking (motor free runs until
DC braking begins),
range is 0.0 to 5.0 sec.
Level of DC braking force,
settable from 0 to 100%
Sets the duration for DC braking,
range
is
from
seconds
Two options; select codes:
00...Edge detection
01...Level detection
Level of DC braking force at
start, settable from 0 to 100%
52
Run
Mode
Lnitial data
Edit
gain
0.0
to
60.0
Defaults
Units
1.0
%
5.0
%
5.0
%
00
00
100.
%
100.
%
100.
100.
100.
100.
00
0.5
Hz
0.0
sec.
50.
%
0.5
sec.
01
0.
%

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents