Func.
Code
D080
Trip counter
D081
Trip monitor 1
D082
Trip monitor 2
D083
Trip monitor 3
d084
Trip monitor 4
d085
Trip monitor 5
d086
Trip monitor 6
d090
Warning monitor
D102
DC bus voltage monitor
d103
BRD load ratio monitor
D104
Electronic thermal monitor
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
"d" Function
Name
Number of trip events,
Range is 0. to 65530
Displays trip event information:
•
Error code
•
Output frequency at trip point
•
Motor current at trip point
•
DC bus voltage at trip point
•
Cumulative inverter operation
time at trip point
•
Cumulative power-ON time at
trip point
Displays the warning code
Voltage of inverter internal DC bus,
Range is 0.0 to 999.9
Usage ratio of integrated brake
chopper, range is 0.0~100.0%
Accumulated
thermal detection, range is from
0.0~100.0%
48
Description
value
of
electronic
Run
Units
Mode
Edit
−
events
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
V
−
%
−
%