NOTE
•
The AC input power cable is not included with the charger.
•
The cable specifications should be determined based on the distance between the distribution panel and the charger,
according to the conditions of the installation work.
•
The disconnect switch should be installed inside the distribution panel of the installation location.
•
The cross-sectional area of the input line/ground line should be at least 6 AWG.
•
Field Wiring Terminal : Use Copper Conductors Only. (Temperature rating : 90 °C (194 °F))
•
Pressure terminal Connector.
Parameter
Wire Size for the terminal block plug
Stud Size for the terminal block plug
Material
Manufacturer
Type
Shape
Required Torque
Specifications
6 AWG
6 mm (0.2 inches)
Oxygen Free Copper
Jeono
JOR-16-6
R-Shape
26 lbf*In / 29.9 kgf*cm
17