34.4. TEST OF ALARM DEVICES (H8/S4)

The programmable outputs of type "Alarm device" or "Alarm device for evacuation" can be collectively activated via this menu (H8/
S4), which makes it possible to test the alarm devices. This procedure includes Addressable siren 4477 and Addressable sounder
base 4479 / 3379, wireless detector 4611, and all alarm devices 4480, 4481, 4482, 4487.
The test cannot be started if a fire alarm already is activated in the system.
One or all control units can be selected. When the test starts, the alarm devices will sound continuously (steady) for approx. 5 sec-
onds, be silent for approx. 25 seconds, sound for approx. 5 seconds and so on.
For the alarm devices 4477, 4479, 3379, 4611, 4480, 4481, 4482, and 4487, the tone with the highest priority level (and type "alarm
device") will be automatically selected.
First replace the sensor and then clear the week average value as soon as possible. Authorised service
personnel only, must do this. Used incorrectly it can cause nuisance fire alarms.
The test will continue for one hour if not stopped via this menu (H8/S4) or if a fire alarm is activated in the system. After one hour,
when the test mode is ended, a message is shown in the General event log (menu H4/U7).
a) Log on to the c.i.e.
b) Navigate to menu S4.
c) Write control unit number and press
OR
d) Press
to select All and press
Press ↵ to start test.
Test of alarm devices control unit: 00
END THE TEST
e) Press
to end the test.
f) To exit the menu press ESC.
to start the test. (All alarm devices in one control unit)
(All alarm devices in all control units.).