Fault Acknowledge (H6) - Panasonic EBL512 G3 Operating Instructions Manual

Hide thumbs Also See for EBL512 G3:
Table of Contents

Advertisement

EBL512 G3 V. 3.0.X - FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS

32. FAULT ACKNOWLEDGE (H6)

Regarding fault indication, and so on., see chapter
See also chapter
22. FAULT ACKNOWLEDGE
All faults and the status / action are stored in the event log and can be listed, see section
In menu H6 can be listed up to 300 faults:
Not corrected (not serviced) and not acknowledged faults (no status information)
Not corrected (not serviced) but acknowledged faults (/Acknowledged)
Corrected (serviced) but not acknowledged faults (/Serviced)
a) Log on to the c.i.e.
b) Navigate to menu H6.
c) Press
or
to scroll in the list:
d) To acknowledge a fault, select it and press
FAULT: Low battery capacity, control unit 00
yyyy-mm-dd hh:mm
FAULT: No reply zone 045 address 06
technical number 000005
yyyy-mm-dd hh:mm
FAULT: No reply zone 021 address 05
technical number 000114
yyyy-mm-dd hh:mm
Fault 1/9 is selected
Previous
page
e) To exit the menu press ESC.
If there are no events --List is empty-- will be shown.
The most recent fault is on top of the list. A serviced fault that is acknowledged will disappear from this list.
20. FAULT
.
.
/Serviced
/Acknowledged
Next
page
and
21. FAULT MESSAGES
113
where all faults messages are listed.
30.7. EVENT LOG (H4/U7)
.