2.2.2 Selection of peripheral devices
(1) Wire size
AC power input terminals R, S, T, motor connection terminals U, V, W, DC
reactor connection terminals P/+, P1, DC terminals P/+, N/-, ground terminals
Terminal
Capacity (K)
Screw Size
0.4
M3.5
0.75
1.5
2.2
M4
3.7
Control circuit terminals (all terminals)
Capacity
Terminal Screw Size Wire Size, Unit: mm
All capacities
Refer to the corresponding instruction manual for wires connection
MEMO
of a stand-alone option connected to the DC terminals P/+, N/-.
Choose the size of the wires connected to the motor connection
terminals so that a voltage drop due to the wires is less than 4V.
The minimum wire size in the above selection table assumes that
the wiring length is less than 20m.
NOTICE
A voltage drop can be found by the following expression:
Line voltage drop (mV) =
Use the ground cable which is as thick as possible.
(2) Crimping terminals
Wire Size, Unit: mm
2
3.5/5.5
Wire Sizes, Unit: mm
R, S, T
U, V, W
2
2
2 to 5.5
2 to 5.5
M2.5
3 × wire resistance (Ω/km)
× wiring length (m) × current (A)
2
Terminal Screw Size
M3.5
M4
M4
2-4