18.4 Troubleshooting for Monitoring

This section describes the countermeasures when GOT does not display the monitor screen.
GOT does not display the screen
POWER LED of GOT is off.
GOT POWER LED is lit in orange
The possible cause is a GOT hardware fault.
Please consult your nearest sales office or FA Center, explaining a detailed description
of the problem.
*1
For utility menu, refer to the following.
*2
For the details of the forced screen saver enable signal, refer to the following.
18 - 10
18.4 Troubleshooting for Monitoring
18.3.3 Specific example of troubleshooting
NO
NO
System Information
function (System Signal 1)
is set.
NO
GOT POWER LED blinks
in orange/green
NO
Chapter 11 DISPLAY AND OPERATION SETTINGS (GOT SET UP)
GT Designer2 Version
GT Designer3 Version1 Screen Design Manual (Fundamentals)
YES
Turn on the power supply of GOT
Backlight OFF during screen saving is set.
YES
The setting of screen saving can be set
in the GOT utility menu. *1
The bit of Forced Screen Saver Enable
YES
Signal may be ON. Confirm the bit status.
When "ON", set the bit to "OFF". *2
Backlight bulb is blown.
YES
To replace the backlight, contact your nearest
sales office or FA Center.