15. Specifications

15.1 Specifications
General Specifications
Measuring range: (measuring range by flow rate conversion)
Combined detector
Measuring range
Combined detector
Measuring range
Combined detector
Measuring range
 
LF622
Accuracy: (Accuracy when combined with the detector)
Combined detector: Small/Middle meter size LF410, LF43*, LF490, GF63* type
Flow rate to the range
(%)
0 〜 20 %
20 〜100 %
0 〜 50 %
50 〜100 %
Combined detector: Small/Middle meter size LF650 type
Flow rate to the range
(%)
0 〜 20 %
20 〜100 %
0 〜 50 %
50 〜100 %
S m a l l / M i d d l e m e t e r s i z e ( 1 5〜 4 5 0 m m ) L F 4 1 0 , L F 4 3 0 , L F 4 9 0 , L F 6 5 0 , G F 6 3 * t y p e
0-0.3m/s to 0-10m/s
(A range of 0-0.1m/s to 0-0.3m/s can be dealt with by an option specified at order time.)
Largel meter size(500〜600mm) LF450, GF63* type
0-0.3m/s to 0-10m/s
Very small meter size(2.5〜6mm) LF470 type
0-0.3m/s to 0-10m/s
0.1 - less than 0.3 m/s
───
───
±0.25 % FS
±0.5 % of rate
0.1 - less than 0.3 m/s
───
───
±0.2 % FS
±0.4% of rate
− 148 −
Accuracy
0.3 - less than 1.0 m/s
───
───
±0.25 % FS
±0.5 % of rate
Accuracy
0.3 - less than 1.0 m/s
───
───
±0.2 % FS
±0.4 % of rate
6 F 8 A 0 9 2 7  
1.0〜10 m/s
±0.1 % FS
±0.5 % of rate
───
───
1.0〜10 m/s
±0.08 % FS
±0.4 % of rate
───
───