ABB RELION REX640 Technical Manual page 842

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
4.4.5.4
Analog channel configuration
MNSPTOC has one analog group input which must be properly configured.
Table 769: Analog inputs
Input
I3P
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
4.4.5.5
Operation principle
The function can be enabled and disabled with the
corresponding parameter values are "On" and "Off".
The operation of MNSPTOC can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
ST_EMERG_ENA
Figure 477: Functional module diagram
Level detector
The calculated negative-sequence current is compared to the
the measured value exceeds the
module.
Timer
Once activated, the timer activates the START output. Depending on the value of
the set
When the operation timer has reached the value set by
mode or the maximum value defined by the inverse time curve, the OPERATE output
is activated.
842
See the preprocessing function blocks in this document for the possible
signal sources.
I3P
BLOCK
Operating curve type , the time characteristics are according to DT or IDMT.
Description
Three-phase currents
Timer
Level
I
2
detector
Start value setting, the function activates the timer
1MRS759142 F
Operation setting. The
OPERATE
t
START
t
BLK_RESTART
Start value setting. If
Operate delay time in the DT
Technical Manual
REX640