ABB RELION REX640 Technical Manual page 713

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Table 661: TR2PTDF Non group settings (Advanced)
Parameter
Values (Range)
Min winding tap
-36...36
Max winding tap
-36...36
Tap nominal
-36...36
Tapped winding
1=Not in use
2=Winding 1
3=Winding 2
Step of tap
0.60...9.00
4.3.2.10
TR2PTDF Monitored data
Table 662: TR2PTDF Monitored data
Name
Type
OPR_A
BOOLEAN
OPR_B
BOOLEAN
OPR_C
BOOLEAN
BLKD2H_A
BOOLEAN
BLKD2H_B
BOOLEAN
BLKD2H_C
BOOLEAN
BLKD5H_A
BOOLEAN
BLKD5H_B
BOOLEAN
Table continues on the next page
REX640
Technical Manual
Unit
Step
1
1
1
%
0.01
Values (Range)
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
Protection functions
Default
17
0
8
1=Not in use
1.50
Unit
Description
Operate phase A
Operate phase B
Operate phase C
2nd harmonic restraint
block phase A status
2nd harmonic restraint
block phase B status
2nd harmonic restraint
block phase C status
5th harmonic restraint
block phase A status
5th harmonic restraint
block phase B status
Description
The tap position
number resulting
the minimum num-
ber of effective
winding turns on
the side of the
transformer where
the tap changer is.
The tap position
number resulting
the maximum num-
ber of effective
winding turns on
the side of the
transformer where
the tap changer is.
The nominal posi-
tion of the tap
changer resulting
the default trans-
formation ratio of
the transformer (as
if there was no tap
changer)
The winding where
the tap changer is
connected to
The percentage
change in voltage
corresponding one
step of the tap
changer
713