ABB RELION REX640 Technical Manual page 833

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
4.4.3.2
Function block
Figure 470: Function block
4.4.3.3
Functionality
The phase discontinuity protection function PDNSPTOC is used for detecting
unbalance situations caused by broken conductors.
The function starts and operates when the unbalance current I
limit. To prevent faulty operation at least one phase current needs to be above the
minimum level. PDNSPTOC operates with DT characteristic.
The function contains a blocking functionality. It is possible to block the function
output, timer or the function itself.
4.4.3.4
Analog channel configuration
PDNSPTOC has one analog group input which must be properly configured.
Table 754: Analog signals
Input
I3P
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
4.4.3.5
Operation principle
The function can be enabled and disabled with the
corresponding parameter values are "On" and "Off".
The operation of PDNSPTOC can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
REX640
Technical Manual
See the preprocessing function blocks in this document for the possible
signal sources.
Protection functions
/I
2
Description
Three-phase currents
Operation setting. The
exceeds the set
1
833