Protection functions
When the bus coupler is in the open position, each section of the busbar handles
the current flow independently, that is, the instantaneous incoming current is equal
to the total instantaneous outgoing current and the difference current is negligible.
The difference current is no longer zero with a fault in the busbar and the protection
operates.
With the bus coupler in the closed position, the current also flows from one busbar
section to another busbar section. Thus, the current flowing through the bus
coupler needs to be considered in calculating differential current. During normal
condition, the summation of the current on each bus section is zero. However, if
there is a fault in any busbar section, the difference current is no longer zero and the
protection operates.
Figure 446: Differential protection on busbar with bus coupler (Single-phase
representation)
4.3.6.7
Example calculations for busbar high-impedance differential
protection
The protected object in the example for busbar differential protection is a single-
bus system with two zones of protection.